Interference Effect between High-Rise Buildings on Local Peak Pressure by Wind Tunnel Test

  • ชุติสุดา ผดุงโอษฐ ภาควิชาวิศวกรรมโยธา คณะวิศวกรรมศาสตร์ มหาวิทยาลัยธรรมศาสตร์
  • Associate Professor Dr. Virote Boonyapinyo DEPARTMENT OF CIVIL ENGINEERING FACULTY OF ENGINEERING, THAMMASAT UNIVERSITY
  • ดร.จิรวัฒน์ จันทร์เรือง มหาวิทยาลัยเทคโนโลยีราชมงคลตะวันออก
Keywords: interference effects, local pressure method, wind tunnel test, interference factor, peak pressure coefficient

Abstract

This research is to study the effect of neighboring buildings in different arrangements on the wind load coefficient of the main building by testing in a wind tunnel using the Local Pressure Measurement method. The wind load coefficients of the main building without adjacent buildings (single building) were compared with the main building that was obscured from neighboring buildings at various distances and presented in the form of wind disturbance factor values. (Interference Factor) in the main building with neighboring buildings at the specified location. The results of the study showed that the wind load coefficients of the main building with neighboring buildings in the oblique manner result in higher maximum suction coefficients than those with neighboring buildings in the same line. The interference effects between the two tall buildings for the maximum pressure coefficients and the maximum suction coefficients at each measurement point of the main building with adjacent buildings are presented and discussed.

Downloads

Download data is not yet available.
Published
2023-07-07
How to Cite
ผดุงโอษฐช., Boonyapinyo, A. P. D. V., & จันทร์เรืองด. (2023). Interference Effect between High-Rise Buildings on Local Peak Pressure by Wind Tunnel Test. The 28th National Convention on Civil Engineering, 28, STR47-1. Retrieved from https://conference.thaince.org/index.php/ncce28/article/view/2145